Benchset
Range - ATC-FO
|
|
| Shutoff capability is directly proportional
to the ability to "load" the actuator up to approximately 18 psig pressure
level. If there is any instrument that will NOT load up to the 18 psig
output pneumatic pressure, the shutoff capability will be reduced. Devices
that can cause a problem by NOT loading up to the 18 psig level are: |
- I/P Transducer with a 3-15 psig output range; the device may only
load up to 16-17 psig level. for the above actuator, the shutoff capability
is "reduced;" i.e. ((16.5-13)/5) x 600 = 420 psid.
|
- Some pneumatic controllers.
|
| A device that DOES unload down to 0 psig is a POSITIONER. |