During
commissioning of a 6000volt, 2000kw Motor powered Forced Draft
Fan, the Fan was center supported by Two Spherical Roller Bearings
(22232),one at each end.
The
fan was producing high noise when running at its rated load and
speed of 1485 rpm. We suspected High Vibrations from unbalance
or Misalignment. When measuring and analyzing vibrations at all
the bearings in Three directions, the levels were NORMAL (Max.
1.9mm/s, at 758Hz in the Fan drive End bearing Axial).
Measurements
at this specific bearing casing were very difficult, since the
analyzer gave an overload signal in any direction of measurement,
and we could not be able to take readings except after ISOLATING
the base of the accelerometer.
Investigating
the bearings showed serrations at the outer race with brownish
marks on the rolling elements, (see attached Photos).
We
suspected PASSING of CURRENT from the bearing casing through the
bearing components ,or from rotor to casing, (Many Photographs
of the Phenomena are available ).
The
Question is :What are the possible Sources of this current leak?.



Click
Here to See Bearing Fault Analysis
Procedure
of Damage Progress in the Forced Draft Fan for
Unit #5 of Aboquir Power Station

|