Electrical Circuit Breakers

By: L. W. Brittian, Mechanical-Electrical Instructor

PART 4


IN THIS THE FOURTH PART OF THE ARTICLE COVERING CIRCUIT BREAKERS, THE FOLLOWING TOPICS ARE COVERED:

TIME CURRENT CURVES
AVAILABLE FAULT CURRENT
SERIES RATED DEVICES
SELECTIVE COORDINATION
LINE AND LOAD TERMINAL CONNECTIONS
AMBIENT COMPENSATED CIRCUIT BREAKERS

TIME CURRENT CURVES

The proper design of an electrical system involves many detailed tasks, such as selection of the circuit breakers that will protect the conductors, equipment, and people who operate the equipment. Proper selection and coordination of breakers for a specific system is facilitated by the use of time current curves. Reading these curves is quite technical and will not be covered in adequate detail to allow someone to properly select OCPD’s; my intention in this short paper is to provide a brief overview only.

Time current curves are plots of the amount of current (vertical scale) flowing in the circuit to the time (horizontal scale) required for the breaker to clear the fault current. Curves are listed by some manufactures as being instantaneous, ultra-short, short, medium, and long.

Melting (eutectic alloy) element type electrical fuses have no moving parts, so no inertial forces need to be overcome for the fuse to open the circuit. Breakers, on the other hand, have parts that must be moved from one position to the other to open the circuit. Generally speaking, fuses (particularly current limiting fuses) can open a circuit faster than circuit breakers. Some solid-state components can be damaged beyond repair in less time than a circuit breaker may be able to open the circuit. For this and other reasons, fuses and not electrical-mechanical circuit breakers best protect some types of electrical components. Restated, you cannot always replace a fuse with a circuit breaker of the same voltage and amperage values.

The time an overcurrent protective device operates can be divided into the following four segments. sensing time: magnetic elements are quicker than thermal elements (which intentionally add delay). Opening time: fuses are quicker than breakers as they have no parts to move. Arcing time: the time during which an arc is present both fuses and breakers have to extinguish the resultant arc. And finally arc extinguishing time: the time the protective device takes to extinguish the fault’s arc varies with the type of device, amperage rating, AIC rating, voltage, and the amount of short circuit or overload current developed.

AVAILABLE FAULT CURRENT

When selecting circuit breakers it is important to know both the maximum continuous amperage and the available fault (short circuit) current. The NEC in article 110.9 provides the following guidance, “ Equipment intended to interupt current at fault levels, shall have an interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment. “ There are two methods commonly used to comply with this NE code requirement.

The most conservative method is to select all OCPD’s based upon the fault current available at the electrical service (or source of supply). For example if 50,000 amps of fault current could be supplied to a building at the service, even the most distant (from the service) branch circuit breaker should be selected to have the ability to safely open the circuit with 50,000 amps of fault current, even though that amount of current would not be available to the line terminals of the most distant circuit protective device. Depending upon the specific nature (such as arcing, or bolted) of the fault, the total amount of fault current available may or may not be developed during operation of the nearest upstream protective device.

SERIES RATED DEVICES

The second method of breaker selection, which is more realistic and more first cost economical, is to select the device(s) based upon the level of fault current that engineering level calculations determine can be potentially available at the device's line terminals.

One may question why spend the extra money purchasing breakers that have a higher AIC than the system can deliver? When it is reasonable to anticipate that the power supply’s capacity will be increased, the initially more costly selection may be justified based upon anticipated system capacity growth.

SELECTIVE COORDINATION

Selective coordination is the selection and application of circuit protective devices in series such that under overload or fault current conditions, only the device just up stream from the overload or fault will open to clear the fault. The remainder of the circuit’s protective devices will remain closed passing power to their individual loads. Selectivity can be based upon time or current levels. This method of selection allows two devices to be connected in series with each other, and seeing the same current level to respond in differing times, the one closest to the fault with the shortest operating time would open the circuit. The device up stream from it, while having the same current level trip point, would have a longer trip delay time, allowing the closer device to react first to open the protected circuit.

If not properly coordinated, the device closest to the fault could have the longer time of response (both having the same current level trip values), and the next protective device up stream could open the circuit, resulting in a potentially more wide spread circuit outage to be experienced by the facility. When the breaker nearest the circuit’s faulted point does not trip yet the one above it does, a review of the degree of coordination should be undertaken.

LINE AND LOAD TERMINAL CONNECTIONS

The terminals at the top of a breaker (when installed in a vertical position) are for connection to the source of supply and are called the line connections (NEMA markings L-1, L-2, L-3, or IEC markings 11, 21,31). The terminals at the bottom of the breaker are for connection to the load (NEMA markings T-1, T-2, T-3, or IEC markings 12, 22, 32). Most breakers must be installed with the source of supply connecting to the top terminals.

Some breakers are listed such that they may be connected to the source of supply either at the top (line) or the bottom (load). These breakers can then be used in a back-fed type of application; that is power can be connected to the bottom (load) of the breaker and the breaker can be used to supply power via its line (top) connections to a bus bar. When a breaker is marked line or load, it must be installed in that manner only. That is line to the source of power and load terminations connected to the utilization equipment. The NEC requires that back-fed type breakers be so installed that it takes more than a pull on the breaker to remove it. See article 408.16 (F) of the 2002 edition.

AMBIENT COMPENSATED CIRCUIT BREAKERS

There are some common installations where the electrical load to be protected will be located in an area that is subject to a different range of environmental conditions, particularly ambient temperature. An extreme example of this type would be where a fan motor is located in a minus 40 degree ice cream freezer and its protective circuit breaker is located in a poorly ventilated motor control center room where the air temperature routinely exceeds 100 degrees F. during hot summer months. This could result in the breaker’s thermal element trip point being reduced due to its hotter ambient. The breaker could experience nuisance tripping.

To avoid temperature related offsets breakers are available with an ambient compensation feature. This design enhancement feature allows the breaker to open the circuit, with out deviation caused by changes in the ambient air temperature within a listed ambient temperature range.

In the next part of this article the following topics will be covered:
• INSULATED CASE CIRCUIT BREAKERS
• ACCESSORIES
• SHUNT TRIP
• AUXILIARY-REMOTE ALARM SWITCH
• GROUND FAULT SENSOR
• UNDER VOLTAGE TRIP
• LOCK-OUT-TAG-OUT PROVISIONS
• REMOTE OPERATOR HANDLE
• STORED ENERGY BREAKER OPERATOR

If you have any questions or comments, please send me an E-mail.

Remember Work Smarter, Not Harder
L. W. Brittian
Mechanical-Electrical Instructor
lwbrittian@hot1.net

 
For more products related to this
topic visit our
Product Showcase

 

For other articles related to this topic visit our Reference Library.


top

 

Need more training?
Search Database of training courses and conferences on these subjects in our 

 Tradeshow/Seminar Search Section

 


top
top
top
 
Current Issue / Archives / Contact Us
© Copyright 2003 Maintenance Resources, Inc.
Phone: 812.877.7119  -  Fax: 812.877.7116  -  E-Mail: info@maintenanceresources.com
Address: 1983 North Hunt Street  -  Terre Haute, IN 47805