Electrical Circuit Breakers

By: L. W. Brittian, Mechanical-Electrical Instructor

Part 7
IN THIS THE FINAL PART OF THE ARTICLE COVERING BREAKERS, THE FOLLOWING TOPICS ARE COVERED:


MICROCOMPUTER CIRCUIT BREAKERS
FIELD SELECTABLE RATING CIRCUIT BREAKERS
OPERATION OVERVIEW
CURRENT SENSING
CONTINUOUS AMPS
LONG TIME DELAY
SHORT TIME PICK-UP
SHORT TIME DELAY
INSTANTANEOUS CURRENT PICK-UP TRIP
GROUND FAULT CURRENT
GROUND FAULT PICK-UP
GROUND FAULT DELAY
VISUAL ANNUNCIATION-INDICATION LAMPS
POWER CONSUMPTION MONITORING
INTERNAL TEST FUNCTIONS

MICROCOMPUTER CIRCUIT BREAKERS

For breakers in sizes above about 500 amps, the need to tailor the breaker’s response increases to the point that a microcomputer-based circuit breaker becomes economical. Load profiles in many commercial/industrial facilities tend to change over time and the ability to tailor a breaker’s specific performance aids in improving the level and types of protection provided for both people and electrical equipment. The following overview will present a brief introduction to some of the more common features available in microcomputer-based breakers that are available today.

The adjustment of any circuit breaker should not to be undertaken too lightly. Almost anyone can turn a setting dial or enter a new value into a computer program. It takes a fair amount of training to be able to commission one of these computerized circuit breakers properly. Unless you have received the specific training needed to correctly adjust one of these units, I suggest that you do not attempt to do so. Just where maintenance task ends and electrical engineering begins should be determined before any adjustments are undertaken. Recall that circuit breakers provide not only protection for equipment, but people as well.

FIELD SELECTABLE RATING CIRCUIT BREAKERS

Some manufactures offer a line of breakers in the 500 to 5,000 amp range that have a replaceable rating plug. These rating plugs allow, for example, a 400 amp frame size breaker to be selected from 200, 225, 250, 300, 350 or 400 amps by the insertion of matching rating plugs. This selectable feature would allow a facility that was anticipating a major increase in load in a few years to initially select a 400 amp frame size breaker with a 225 amp rating plug to be installed. When the load increased in the future, the breaker could have its amperage rating increased by the quick replacement of the rating plug. Various selectable values for these types of breakers are based upon either percentages or multiples of the basic continuous current rating of the installed rating plug.

OPERATION OVERVIEW

Current data is obtained for each phase from current transformers (CT) mounted within the breaker. The CT output signals are converted to digital values and sent to a microcomputer. The microprocessor monitors each phase individually at a very high sampling rate. This is a key improvement in identifying current and voltage waveforms. The microcomputer then determines when the circuit breaker should trip due to an overcurrent condition. An electro-magnetic latch unit in the breaker causes the breaker to trip upon receipt of a trip signal from the microcomputer. This allows the shape of the breaker’s time current curve to be manipulated electronically and to be tailored to fit the desired performance profile in most every detail.

The ability to field program the microprocessor to accomplish the desired response to various values of time and current offers a level of circuit protection never before possible. With the addition of an external communications link (LAN or Ethernet type gateway) individual breakers can be communicated with, monitored, re-programmed, controlled, and coordinated from any compatible connected location, be it locally or from a distant central control room.

Many of these breakers have the ability to record past events such as the cause of the individual trip events, date and time of past trips, voltage and current values, or waveforms on all three phases and the neutral.

CURRENT SENSING

The use of microcomputers has allowed for many improvements to be made in circuit protective devices. One area is in the sensing of current. Some breakers sense an average of the current, while others sense only the peak currents generated in a sine wave. This is fine if the circuit’s current waveform is that of a true sine wave, which few are.

The increased use of ultra fast power switching devices has resulted in harmonic distortions becoming increasingly more common. With microcomputer-equipped breakers, the true RMS value can be determined even with harmonic distortions. The microcomputer is able to take many samples of the current’s waveform per second. The microcomputer then uses these samples to calculate the true RMS value of the load current. This allows the breaker to perform faster, and with greater accuracy than ever before.

The AFCI feature of molded case low voltage circuit breakers has been made possible by advances in current transformers capable of responding to very high frequency currents; in turn the microcomputer has allowed the data to be analyzed, classified, plotted, stored and when so required to be displayed for visual review and analysis.

CONTINUOUS AMPS

Continuous ampere is a percentage of the circuit breaker’s normal current rating. Continuous amps can be adjusted typically from 20 to 100 % of the breaker’s nominal rating (for example, If the plug unit selected is 1,000 amps, 100 % would be 1,000 amps. A setting of 50% would result in decreasing the continuous load amps to 500 amps.

LONG TIME DELAY

The long time delay causes the breaker to wait a certain amount of time to allow for temporary inrush currents to subside, such as those caused from motor starting locked rotor currents, without the breaker tripping. The long time delay function setting is the length of time the breaker will hold an overload (running overcurrent) before causing the breaker to open.

SHORT TIME PICK-UP

This function’s setting will determine the amount of current the breaker will carry for a short time period, allowing down stream circuit protective devices to open the circuit and clear the fault without tripping the up stream breaker. This allows for fine-tuning of the selective clearing function of the breaker.

This function is typically adjustable from one and one half to ten times the trip unit ampere setting. For example, a 1,000 ampere frame can be adjusted to trip anywhere from 1,500 to 10,000 amps. This is the amount of current the breaker must see in order for it to respond.

SHORT TIME DELAY

The short time delay is used in conjunction with the short time pickup and controls the amount of time involved in postponing a short time pickup operation. This is the amount of time that must elapse before causing the breaker to open the circuit. This feature allows better coordination with downstream OCPD’s.

INSTANTANEOUS CURRENT PICKUP

This feature’s setting is used to trip the circuit breaker with no intentional delay at any current typically between two and forty times the breaker’s continuous ampere setting. For example assume the instaneous pickup has been set to ten times the continuous amp setting or 10,000 amps (10 x 1,000) with a continuous amp setting of 1,000 amps. In this case a higher setting would trip at 10,000 amps due to a fixed instantaneous override of 10,000 amps, which automatically trips the circuit breaker regardless of the instantaneous pickup setting. If the continuous amp setting had been 300 amps, the instaneous pickup setting at ten would make the instantaneous setting equal to 3,000 amps, well below the fixed instantaneous override. This function is much the same as the magnetic trip unit’s instantaneous pick-up only programmable for the specific needs of the unique installation.

GROUND FAULT CURRENT

Typically an LED type of display provides a reading of the number of amps flowing across the equipment grounding conductor. The ground fault monitor can be utilized with a display module or a relay that has a set of contacts for a ground fault alarm. When used with a shunt trip equipped breaker, a ground fault monitor can be used for ground fault tripping of a breaker equipped with a shunt trip feature.

GROUND FAULT PICKUP

This adjustment controls the amount of ground fault current that will cause the breaker to open. These adjustments typically range from 20 to 70% of the maximum breaker rating in compliance with article 230.95 (A) of the NEC that no pickup setting exceeds 1200 amps. Ground fault pickup is sometimes divided into sections that allow various time delay values to be added to the breaker’s trip point when a ground fault occurs. This feature is useful for improving circuit breaker coordination with both up and down stream protective devices.

GROUND FAULT DELAY

This is the time period that must pass before the breaker trips. This feature’s setting is typically one of two types, an inverse time or a constant amount of time delay. The inverse time method shortens the amount of delay as the amount of ground fault current increases. Please recall that the longer a fault exists and the higher the current flowing in the faulted circuit, the more potential danger and damage there will be. The constant amount of time delay method maintains the time delay period the same no matter what the amplitude of the fault current may be.

VISUAL ANNUNCIATION-INDICATION LAMPS

Depending upon the brand and model, various lights give the user a means for visually determining what type of fault caused the breaker to open. Typically indicator lamps are provided for indication of long time fault, short time fault, instantaneous fault, and ground fault events.

POWER CONSUMPTION MONITORING

Some models can be equipped with features to assist in monitoring electrical energy consumption. Data displays are the common seven segment LEDs. Adjustable alarm set points may also be provided on some models. Various communication protocols are used by individual manufactures. With increasing concerns about power quality, this feature is being expanded to include factors relating to power quality and not just power quantity.

INTERNAL TEST FUNCTIONS

This feature enables the user to test the microcomputer’s trip circuit’s electronics, the electro-magnetic latch and power contact set opening mechanism. The purpose of this test function is to provide the user with an easy means to conduct a quick go-no-go type of test before bringing the circuit breaker on-line to protect and pass power to the connected loads.

Some manufactures provide for some degree of automatic testing each time the system is powered up. With yet others individual test are carried out manually following predetermined steps. The testing of many of these complex breakers cannot be done until all of the field selectable and variable values have been entered, or default values (where provided) have been selected. Many of these internal test functions are covered under the label of a “watchdog timer” that monitors the processor’s health for indications of non-performance (within specified times). The concept of intelligent electrical devices has long been out of the lab and has been broadly integrated into the “plant floor”.

If we could give Mr. Edison one of these modern replacements for his lead wire fuse, I wonder what he would do with it? My bet is just what manufactures are doing today, try and make them better.

ENVIRONMENTAL IMPACT STATEMENT

I do not intend what you likely anticipate that the above implies. “No man is an island”. That is the things that go on around each of us (our environment) have an impact upon each of us, and boy oh boy have I been impacted. So much so that I doubt that there is a single original idea contained in these pages. From my first grade ABC’s teacher to more than one professional electrical engineer, lots of good folks have directly and indirectly helped me to write this article, so many so that I cannot accurately recall all of them. Instead I chose to list only one. Mr. Holt from center of my being Thank you!.. Sir. May God bless and keep you and yours safe!

This concludes this series of articles covering circuit breakers. I hope that you will continue your study of circuit and overcurrent protective devices. If you have any questions or comments, please send me an E-mail.

If you have any questions or comments, please send me an E-mail.

Remember Work Smarter, Not Harder
L. W. Brittian
Mechanical-Electrical Instructor
lwbrittian@hot1.net

 
For more products related to this
topic visit our
Product Showcase

 

For other articles related to this topic visit our Reference Library.


top

 

Need more training?
Search Database of training courses and conferences on these subjects in our 

 Tradeshow/Seminar Search Section

 


top
top
top
 
Current Issue / Archives / Contact Us
© Copyright 2003 Maintenance Resources, Inc.
Phone: 812.877.7119  -  Fax: 812.877.7116  -  E-Mail: info@maintenanceresources.com
Address: 1983 North Hunt Street  -  Terre Haute, IN 47805