NFPA
70B Recommended Practice for
Electrical Equipment Maintenance
by
Steven J. Owen, electrical consultant
The purpose of this document is to give recommendations
for the maintenance of various types of electrical installations,
apparatus, and equipment usually found in industrial and
large commercial-type installations. Generally speaking,
it is recognized that maintenance needs for specific types
of equipment is provided by the equipment manufacturer,
as well as from a number of other sources. This is the reason
why this standard was developed. The purpose was to bring
the general guidelines from various sources into one document
– NFPA 70B Recommended Practice for Electrical Equipment
Maintenance.
The first three chapters are intended to provide a better
understanding of benefits, both direct and intangible, that
can be derived for a well-administered EPM program. This
recommended practice is confined to preventive maintenance
for industrial-type electrical systems and equipment and
is not intended to supplicate or supersede instructions
that the electrical manufacturers normally provide. Consumer
appliances and equipment intended primarily for use in the
home are not included.
Chapter 4 addresses planning and developing an electrical
preventative maintenance program (EPM). There are four basic
steps … (1) compile a listing of all plant equipment
and systems; (2) determine which equipment and systems are
most critical and most important; (3) develop a system for
keeping up with what needs to be done; (4) train people
for the work that needs to be done, or contract for the
special services that are needed.
This standard covers equipment ranging from substations
and switchgear assemblies, to power and distribution transformers;
wiring devices; portable electrical tools and equipment.
Let’s discuss a few of the items.
Motor control equipment is found in Chapter 9. Make sure
that internal heating, cooling, or air conditioning systems
functions properly, as designed. Busbar and terminal connections
should be checked for tightness, i.e, not being loose, which
leads to proper torque requirements. Pay special attention
to aluminum connections. Check busbar support insulators
and barriers to ensure that they are free of contamination.
Look for cracks and signs of arc tracking. Replace defective
units. Don’t forget to check control circuit wiring,
at the least annually. Visually check for evidence of damage
from over- heating or chafing.
I have a surprise for all of you readers. According to
Chapter 9, Section 9-3.5, temporary wiring should be removed
or replaced by permanent wiring. How many different standards
have to remind us to do this? The 1999 National Electrical
Code in Section 305-3(d), or the 2002 National Electrical
Code in Section 527.3(D) make it very clear that temporary
wiring must be removed immediately upon completion of construction,
or for the purpose for which it was installed. OSHA has
the same requirement in the Construction Standard 29CFR
1926, Section 1926.405(a)(2).
Section 9-4 of NFPA 70B addresses an item that is commonly
overlooked. Disconnects, i.e., motor disconnects, when not
properly maintained have been known to fail, some- times
with catastrophic results. Failing disconnects have led
to serious injuries to personnel operating them.
Chapter 11 addresses molded-case circuit-breaker power
panels. Section 11-4 recognizes that standard molded-case
circuit breakers are not generally equipped with ground-fault
sensing and protection devices, therefore, will not normally
trip and clear low-level ground-faults, which can do immense
damage, including causing fires. Where necessary, special
ground-fault sensing and protective devices may be specified
and installed as part of the circuit breaker. Maintenance
of molded-case circuit breakers is divided into two parts
– electrical and mechanical. Remember, there is a
trip, and a latch mechanism that need to exercised routinely.
Inspection and cleaning is also part of the maintenance.
Chapter 12 addresses ground-fault protection. There two
types of protection; (1) ground-fault-circuit-interrupter
protection for personnel (Class A, 5 milliampere differential
trip);
(2) ground-fault protection for equipment (differential
protection more than 5 milli- amperes), with differential
trip settings of 10, 20, or 30 milliamperes, or more.
Check your GFCI circuit breakers, receptacles and other
devices at the intervals specified by the manufacturer.
Tests conducted have shown that a surprisingly large number
of ground-fault circuit-interrupters (Class A) fail when
tested. The National Electrical Safety Foundation and the
Consumer Product Safety Commission jointly issued a “consumer
awareness” recommendation to check GFCI’s monthly
and after storms.
Chapter 17 of NFPA 79B, addresses portable electrical tools
and equipment. Train your people, check and maintain your
equipment on a daily basis (as OSHA mandates), repair as
necessary. This is also similar to 1999 NEC Section 305-6
(b)(2)(a)(3).
There is much more information in NFPA 79B than what I
have outlined in this article; i.e., power quality, UPS
systems, cable trays and busways, lighting, rotating equipment,
vibration analysis, etc. Please obtain a copy of NFPA 79B
for your library.
Conclusion:
The purpose of NFPA 79B is to reduce hazards to life and
property that can result from failure or malfunction of
industrial-type electrical systems and equipment. Good work
practices would promote using this Standard for all electrical
equipment, not industrial equipment and systems only. Like
all other NFPA Standards, this Standard is not enforceable
by itself, however, any company and / or employer can adopt
this Standard and choose to voluntarily follow the recommended
practices. It is not mandatory, rather, it is a common sense
approach to protecting people and property, and prolonging
the life of the equipment and systems.
References:
NFPA 70-1999, National Electrical Code, (National Fire
Protection Association, Quincy, MA), Section 305-6.
NFPA 70-2002, National Electrical Code, (National Fire
Protection Association, Quincy, MA), Section 527-3(D), Section
527-6.
OSHA (Construction Standard), 29CFR 1926. Section 1926.405(a)(2).
NFPA 70E-2000, Standard for Electrical Safety Requirements
for Employee Workplaces, (Quincy, MA, National Fire Protection
Association).
NFPA 70B-1998, Recommended Practice of Electrical Equipment
Maintenance, (Quincy, MA, National Fire Protection Association).
NESF: National Electrical Safety Foundation; “Test
and Protect GFCI” awareness campaign.
Steven J. Owen, electrical consultant, has been active
in the electrical industry for over 26 years. Owen is certified
as a master electrician/contractor in 45 states; as a National
Electric Code instructor for continuing education in 25
states; as an OSHA authorized trainer for Construction and
General Industry; as an electrical inspector by BOCA, CABO,
IAEI, ICBO & SBCCI; as a Chief Code Analyst by SBCCI;
as a lightning protection designer, inspector, installer
by LPI; as a Power Distribution Engineering Technician by
NICET; Principal voting member of CMP-3 of NFPA 70 –
NEC; as a member of ABC, ASCET, ASSE, IAEI, NETA, NFPA,
NICET, RSES and SBCCI.
|